Moxa Technologies E Series User Manual

Browse online or download User Manual for Networking Moxa Technologies E Series. Moxa Technologies E Series User`s manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Moxa Technologies Co., Ltd

ioLogik R2140 User’s Manual First Edition, January 2007 www.moxa.com/product Moxa Technologies Co., Ltd. Tel: +886-2-8919-1230 Fax: +886-2-8919-1231

Page 2 - Disclaimer

22 Chapter 2. Initial Setup This chapter describes how to install the ioLogik R2140. The following topics are covered:  Hardware Installation ¾ Co

Page 3 - Table of Contents

ioLogik R2140 User’s Manual Initial Setup Hardware Installation Connecting the Power Connect the 12 to 48 VDC power line to the ioLogik R2140’s ter

Page 4

ioLogik R2140 User’s Manual Initial Setup Modbus/RTU Devices The RS-485 port runs Modbus/RTU and can connect to any Modbus device. You may use diff

Page 5

ioLogik R2140 User’s Manual Initial Setup You may click “Stop” as soon as your ioLogik R2140 appears on the list. Otherwise, ioAdmin will contin

Page 6 - Packing List

33 Chapter 3. Using ioAdmin This chapter goes over the functions available in ioAdmin, the main configuration and management utility for the ioLogi

Page 7 - Product Specifications

ioLogik R2140 User’s Manual Using ioAdmin Introduction to ioAdmin ioLogik remote I/O servers may be managed and configured over the RS-485 bus by ioA

Page 8 - Physical Dimensions

ioLogik R2140 User’s Manual Using ioAdmin Configuration File ioAdmin allows the configuration of the ioLogik R2140 to be saved as a file. The file is

Page 9 - Hardware Reference

ioLogik R2140 User’s Manual Using ioAdmin ioAdmin Main Screen Main Screen Overview ioAdmin’s main screen is shown below. The main window defaults to

Page 10 - Initial Setup

ioLogik R2140 User’s Manual Using ioAdmin You may also access the wiring guide through the Help menu on the menu bar. 3-5

Page 11 - Hardware Installation

ioLogik R2140 User’s Manual Using ioAdmin I/O Configuration Tab (General) The I/O Configuration tab shows the status of every I/O channel underneath

Page 12 - Software Installation

ioLogik R2140 User’s Manual The software described in this manual is furnished under a license agreement, and may be used only in accordance with the

Page 13 - MXIO Library

ioLogik R2140 User’s Manual Using ioAdmin Server Settings Tab (General) The Server Settings tab is where you log in as an administrator. This is requ

Page 14 - Using ioAdmin

ioLogik R2140 User’s Manual Using ioAdmin I/O Configuration Tab (Administrator) When logged on as an administrator, you may double click on a channel

Page 15 - Features of ioAdmin

ioLogik R2140 User’s Manual Using ioAdmin Host Connection Watchdog is disabled, the ioLogik R2140 will never enter Safe Status and the Safe Status se

Page 16 - Using ioAdmin

ioLogik R2140 User’s Manual Using ioAdmin Firmware Update Tab The ioLogik R2140 supports remote firmware updates through the Firmware Update tab. Ent

Page 17 - Wiring Guide

ioLogik R2140 User’s Manual Using ioAdmin Server Context Menu The Server context menu is accessed by right clicking on the server model name in the

Page 18

ioLogik R2140 User’s Manual Using ioAdmin ioLogik R2140 Network I/O Server Configuration ============================================= Date: 2006/11

Page 19 - Server Info Tab

44 Chapter 4. Cascading with Other I/O Servers The ioLogik R2140 can act both as a standalone I/O server and as an extension module to other I/O r

Page 20

ioLogik R2140 User’s Manual Cascading with Other I/O Servers Introduction The ioLogik R2140 can serve as an extension module to provide additional I/

Page 21

ioLogik R2140 User’s Manual Cascading with Other I/O Servers 2. In ioAdmin, click the E2210 in the navigation panel and select “Add Serial I/O Serve

Page 22

ioLogik R2140 User’s Manual Cascading with Other I/O Servers 4. The R2110 will appear with its unit ID under the E2210 in ioAdmin’s navigation panel

Page 23 - Watchdog Tab

Table of Contents Chapter 1. Introduction ...1-1 Overvi

Page 24 - Server Context Menu

ioLogik R2140 User’s Manual Cascading with Other I/O Servers 3. Select the appropriate I/O Server type and UnitID (“R2110 RS-485” and “2” in this ex

Page 25 - Import System Config

ioLogik R2140 User’s Manual Cascading with Other I/O Servers 5. Both the R2110 and R2140 will appear with their unit IDs under the E2210 in ioAdmin’

Page 26

AA Appendix A. Liquid Crystal Display Module (LCM) As an Easy View device, the ioLogik R2140 supports an optional detachable Liquid Crystal Display

Page 27 - Cascading System Bus

ioLogik R2140 User’s Manual Liquid Crystal Display Module (LCM) A-2Display Explanation / Actions <ioLogik R2140> i/o setting Enter this subme

Page 28

BBAppendix B. Modbus/RTU Address Mappings 0xxxx Read/Write Coils (Support function 1, 5,15) Reference Address Data Type Description 00001 0x0000

Page 29

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Reference Address Data Type Description 00010 0x0009 1bit Reset CH1 AI Max Value Read: al

Page 30

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Reference Address Data Type Description 30020 0x0013 1 word CH3 Read AI Max Value 30021

Page 31 - Limitations

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x000D 1 word CH1 AI Range 00: +/-150 mV 01: +/-500 mV 02: +/

Page 32 - Options

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x0013 1 word CH7 AI Range 00: +/-150 mV 01: +/-500 mV 02: +/

Page 33 - <ioLogik R2140>

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x0019 1 word CH5 AI PowerOn Range 00: +/-150 mV 01: +/-500

Page 34 - Modbus/RTU Address Mappings

3xxxx Read only Registers (Support function 4)...B-2 4xxxx Read/Write Registers (Suppo

Page 35

ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x001F 1 word CH3 AI Safe Range 00: +/-150 mV 01: +/-500 mV

Page 36

CC Appendix C. Factory Default Settings The ioLogik R2140 is configured with the following factory defaults: RS-485 Unit ID: 1 Default baud ra

Page 37

DD Appendix D. Pinouts and Cable Wiring Serial Port Pinouts R2140 RS-485 Modbus Adapter Pin Assignment Pin Assignment of Terminal Blocks Power/RS-

Page 38

ioLogik R2140 User’s Manual Pinouts and Cable Wiring I/O Device Wiring Function Diagram AO Schematic MCU DAC Vout+-Iout AIN Sc

Page 39

EE Appendix E. Service Information This appendix shows you how to contact MOXA for information about the ioLogik R2140, and other products, and how

Page 40 - Function 8

ioLogik R2140 User’s Manual Service Information MOXA Internet Services Customer satisfaction is our top priority. To ensure that customers receive th

Page 41 - Factory Default Settings

ioLogik R2140 User’s Manual Service Information Problem Report Form MOXA ioLogik R2140 Remote I/O Server Customer name: Company: Tel: Fax: Email: Dat

Page 42 - Pinouts and Cable Wiring

ioLogik R2140 User’s Manual Service Information Product Return Procedure For product repair, exchange, or refund, the customer must complete each of

Page 43 - Function Diagram

11 Chapter 1. Introduction The ioLogik R2140 is a stand-alone remote I/O server that can connect sensors for automation applications over an RS-485

Page 44 - Service Information

ioLogik R2140 User’s Manual Introduction Overview The ioLogik R2140 is part of the R2000 series of ioLogik remote I/O servers, which are designed to

Page 45 - MOXA Internet Services

ioLogik R2140 User’s Manual Introduction Product Specifications Serial Interface RS-485 (2-wire): Data+, Data-, GND Serial line protection 15 KV ES

Page 46 - Problem Report Form

ioLogik R2140 User’s Manual Introduction Agency Approvals EMI FCC Part 15, CISPR (EN55022) Class A EMS IEC61000-4-2 (ESD), level 2/3, IEC61000-4-3

Page 47 - Product Return Procedure

ioLogik R2140 User’s Manual Introduction Hardware Reference Panel Guide NOTE – The reset button restores the factory default settings. Hold the but