ioLogik R2140 User’s Manual First Edition, January 2007 www.moxa.com/product Moxa Technologies Co., Ltd. Tel: +886-2-8919-1230 Fax: +886-2-8919-1231
22 Chapter 2. Initial Setup This chapter describes how to install the ioLogik R2140. The following topics are covered: Hardware Installation ¾ Co
ioLogik R2140 User’s Manual Initial Setup Hardware Installation Connecting the Power Connect the 12 to 48 VDC power line to the ioLogik R2140’s ter
ioLogik R2140 User’s Manual Initial Setup Modbus/RTU Devices The RS-485 port runs Modbus/RTU and can connect to any Modbus device. You may use diff
ioLogik R2140 User’s Manual Initial Setup You may click “Stop” as soon as your ioLogik R2140 appears on the list. Otherwise, ioAdmin will contin
33 Chapter 3. Using ioAdmin This chapter goes over the functions available in ioAdmin, the main configuration and management utility for the ioLogi
ioLogik R2140 User’s Manual Using ioAdmin Introduction to ioAdmin ioLogik remote I/O servers may be managed and configured over the RS-485 bus by ioA
ioLogik R2140 User’s Manual Using ioAdmin Configuration File ioAdmin allows the configuration of the ioLogik R2140 to be saved as a file. The file is
ioLogik R2140 User’s Manual Using ioAdmin ioAdmin Main Screen Main Screen Overview ioAdmin’s main screen is shown below. The main window defaults to
ioLogik R2140 User’s Manual Using ioAdmin You may also access the wiring guide through the Help menu on the menu bar. 3-5
ioLogik R2140 User’s Manual Using ioAdmin I/O Configuration Tab (General) The I/O Configuration tab shows the status of every I/O channel underneath
ioLogik R2140 User’s Manual The software described in this manual is furnished under a license agreement, and may be used only in accordance with the
ioLogik R2140 User’s Manual Using ioAdmin Server Settings Tab (General) The Server Settings tab is where you log in as an administrator. This is requ
ioLogik R2140 User’s Manual Using ioAdmin I/O Configuration Tab (Administrator) When logged on as an administrator, you may double click on a channel
ioLogik R2140 User’s Manual Using ioAdmin Host Connection Watchdog is disabled, the ioLogik R2140 will never enter Safe Status and the Safe Status se
ioLogik R2140 User’s Manual Using ioAdmin Firmware Update Tab The ioLogik R2140 supports remote firmware updates through the Firmware Update tab. Ent
ioLogik R2140 User’s Manual Using ioAdmin Server Context Menu The Server context menu is accessed by right clicking on the server model name in the
ioLogik R2140 User’s Manual Using ioAdmin ioLogik R2140 Network I/O Server Configuration ============================================= Date: 2006/11
44 Chapter 4. Cascading with Other I/O Servers The ioLogik R2140 can act both as a standalone I/O server and as an extension module to other I/O r
ioLogik R2140 User’s Manual Cascading with Other I/O Servers Introduction The ioLogik R2140 can serve as an extension module to provide additional I/
ioLogik R2140 User’s Manual Cascading with Other I/O Servers 2. In ioAdmin, click the E2210 in the navigation panel and select “Add Serial I/O Serve
ioLogik R2140 User’s Manual Cascading with Other I/O Servers 4. The R2110 will appear with its unit ID under the E2210 in ioAdmin’s navigation panel
Table of Contents Chapter 1. Introduction ...1-1 Overvi
ioLogik R2140 User’s Manual Cascading with Other I/O Servers 3. Select the appropriate I/O Server type and UnitID (“R2110 RS-485” and “2” in this ex
ioLogik R2140 User’s Manual Cascading with Other I/O Servers 5. Both the R2110 and R2140 will appear with their unit IDs under the E2210 in ioAdmin’
AA Appendix A. Liquid Crystal Display Module (LCM) As an Easy View device, the ioLogik R2140 supports an optional detachable Liquid Crystal Display
ioLogik R2140 User’s Manual Liquid Crystal Display Module (LCM) A-2Display Explanation / Actions <ioLogik R2140> i/o setting Enter this subme
BBAppendix B. Modbus/RTU Address Mappings 0xxxx Read/Write Coils (Support function 1, 5,15) Reference Address Data Type Description 00001 0x0000
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Reference Address Data Type Description 00010 0x0009 1bit Reset CH1 AI Max Value Read: al
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Reference Address Data Type Description 30020 0x0013 1 word CH3 Read AI Max Value 30021
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x000D 1 word CH1 AI Range 00: +/-150 mV 01: +/-500 mV 02: +/
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x0013 1 word CH7 AI Range 00: +/-150 mV 01: +/-500 mV 02: +/
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x0019 1 word CH5 AI PowerOn Range 00: +/-150 mV 01: +/-500
3xxxx Read only Registers (Support function 4)...B-2 4xxxx Read/Write Registers (Suppo
ioLogik R2140 User’s Manual Modbus/TCP Address Mappings Address Data Type Description 0x001F 1 word CH3 AI Safe Range 00: +/-150 mV 01: +/-500 mV
CC Appendix C. Factory Default Settings The ioLogik R2140 is configured with the following factory defaults: RS-485 Unit ID: 1 Default baud ra
DD Appendix D. Pinouts and Cable Wiring Serial Port Pinouts R2140 RS-485 Modbus Adapter Pin Assignment Pin Assignment of Terminal Blocks Power/RS-
ioLogik R2140 User’s Manual Pinouts and Cable Wiring I/O Device Wiring Function Diagram AO Schematic MCU DAC Vout+-Iout AIN Sc
EE Appendix E. Service Information This appendix shows you how to contact MOXA for information about the ioLogik R2140, and other products, and how
ioLogik R2140 User’s Manual Service Information MOXA Internet Services Customer satisfaction is our top priority. To ensure that customers receive th
ioLogik R2140 User’s Manual Service Information Problem Report Form MOXA ioLogik R2140 Remote I/O Server Customer name: Company: Tel: Fax: Email: Dat
ioLogik R2140 User’s Manual Service Information Product Return Procedure For product repair, exchange, or refund, the customer must complete each of
11 Chapter 1. Introduction The ioLogik R2140 is a stand-alone remote I/O server that can connect sensors for automation applications over an RS-485
ioLogik R2140 User’s Manual Introduction Overview The ioLogik R2140 is part of the R2000 series of ioLogik remote I/O servers, which are designed to
ioLogik R2140 User’s Manual Introduction Product Specifications Serial Interface RS-485 (2-wire): Data+, Data-, GND Serial line protection 15 KV ES
ioLogik R2140 User’s Manual Introduction Agency Approvals EMI FCC Part 15, CISPR (EN55022) Class A EMS IEC61000-4-2 (ESD), level 2/3, IEC61000-4-3
ioLogik R2140 User’s Manual Introduction Hardware Reference Panel Guide NOTE – The reset button restores the factory default settings. Hold the but